Table 636: VNMMXU Non group settings (advanced)
Name Values (Range) Unit Step Default Description
UL1HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL1HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL1LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL1LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
100% of Ur
UL1Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL2HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL2HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL2LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL2LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UL2Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL3HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL3HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL3LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL3LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UL3Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
16.1.6 Monitored data
Table 637: CVMMXN Monitored data
Name
Type Values (Range) Unit Description
S REAL - MVA Apparent Power
magnitude of deadband
value
P
REAL - MW Active Power magnitude
of deadband value
Q REAL - MVAr Reactive Power
magnitude of deadband
value
PF
REAL - - Power Factor magnitude
of deadband value
U REAL - kV Calculated voltage
magnitude of deadband
value
I
REAL - A Calculated current
magnitude of deadband
value
F
REAL - Hz System frequency
magnitude of deadband
value
1MRK502052-UEN B Section 16
Monitoring
875
Technical manual