Name Values (Range) Unit Step Default Description
EARAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active reverse
accumulated energy value
ERFAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive forward
accumulated energy value
ERRAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive reverse
accumulated energy value
Table 718: ETPMMTR Non group settings (advanced)
Name Values (Range) Unit Step Default Description
EALim 0.001 -
10000000000.000
MWh 0.001 1000000.000 Active energy limit
ERLim 0.001 -
10000000000.000
MVArh 0.001 1000.000 Reactive energy limit
EnZeroClamp Off
On
- - On Enable of zero point clamping detection
function
LevZeroClampP 0.001 - 10000.000 MW 0.001 10.000 Zero point clamping level at active Power
LevZeroClampQ 0.001 - 10000.000 MVAr 0.001 10.000 Zero point clamping level at reactive
Power
DirEnergyAct Forward
Reverse
- - Forward Direction of active energy flow Forward/
Reverse
DirEnergyReac Forward
Reverse
- - Forward Direction of reactive energy flow Forward/
Reverse
EAFPrestVal 0.000 -
100000000.000
MWh 0.001 0.000 Preset Initial value for forward active
energy
EARPrestVal 0.000 -
100000000.000
MWh 0.001 0.000 Preset Initial value for reverse active
energy
ERFPresetVal 0.000 -
100000000.000
MVArh 0.001 0.000 Preset Initial value for forward reactive
energy
ERRPresetVal 0.000 -
100000000.000
MVArh 0.001 0.000 Preset Initial value for reverse reactive
energy
17.2.6 Monitored data
Table 719: ETPMMTR Monitored data
Name
Type Values (Range) Unit Description
EAFACC REAL - MWh Accumulated forward
active energy value in Ws
EARACC REAL - MWh Accumulated reverse
active energy value in Ws
ERFACC REAL - MVArh Accumulated forward
reactive energy value in
VArS
ERRACC
REAL - MVArh Accumulated reverse
reactive energy value in
VArS
Table continues on next page
Section 17 1MRK502052-UEN B
Metering
988
Technical manual