IEC140000126 V2 EN
Figure 46: PMUREPORT settings in PCM600 PST
Figure 47 shows an example of correct connection of SMAI and PHASORREPORT
blocks in ACT where two different SMAI blocks are connected to different
PHASORREPORT blocks with different instance numbers. In this example, as the
PHASORREPORT blocks have different instance numbers and different settings for
SvcClass and ReportRate, a separate SMAI block is used for each PHASORREPORT
block.
IEC140000127 V2 EN
Figure 47: An example of correct connection of SMAI and PHASORREPORT
blocks in ACT
Figure 48 shows an example of wrong connection of SMAI and PHASORREPORT
blocks in ACT where the same SMAI block is connected to different
PHASORREPORT blocks with different instance numbers. Such connection will be
only correct if both connected PHASORREPORT blocks have similar settings for
SvcClass and ReportRate. If settings for PMUREPORT instances differ for SvcClass
or ReportRate, then PHASOR1 connection in PHASORREPORT1 instance 2 will not
1MRK 502 071-UEN - Section 6
Wide area measurement system