EasyManua.ls Logo

ABB REG670 - Page 188

ABB REG670
780 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
level can be required. The setting is normally 1.0 but in multi-breaker arrangement the
setting shall be CT primary rating/IBase.
CTFactorPri2: A factor to allow a sensitive function also at multi-breaker
arrangement where the rating in the bay is much higher than the rated current of the
transformer winding. The stabilizing can then be high so an unnecessary high fault
level can be required. The setting is normally 1.0 but in multi-breaker arrangement the
setting shall be CT primary rating/IBase.
CTFactorSec1: See setting CTFactorPri1. Only difference is that CTFactorSec1 is
related to W2 side.
CTFactorSec2: See setting CTFactorPri2. Only difference is that CTFactorSec2 is
related to W2 side.
Section 7 1MRK 502 071-UEN -
Differential protection
182 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual

Table of Contents

Other manuals for ABB REG670

Related product manuals