Parallel line out of service and not earthed
Z
0m
A B
Z< Z<
IEC09000254_1_en.vsd
IEC09000254 V1 EN
Figure 88: Parallel line is out of service and not earthed
When the parallel line is out of service and not earthed, the zero sequence on that line
can only flow through the line admittance to the earth. The line admittance is high
which limits the zero-sequence current on the parallel line to very low values. In
practice, the equivalent zero-sequence impedance circuit for faults at the remote bus
bar can be simplified to the circuit shown in figure
88
The line zero sequence mutual impedance does not influence the measurement of the
distance protection in a faulty circuit. This means that the reach of the underreaching
distance protection zone is reduced if, due to operating conditions, the equivalent zero
sequence impedance is set according to the conditions when the parallel system is out
of operation and earthed at both ends.
A
B
C
IEC09000255_1_en.vsd
I
0
I
0
Z
0m
Z
0
-
Z
0m
Z
0m
Z
0
-
IEC09000255 V1 EN
Figure 89: Equivalent zero-sequence impedance circuit for a double-circuit line
with one circuit disconnected and not earthed
The reduction of the reach is equal to equation 51.
1MRK 502 071-UEN - Section 8
Impedance protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 199
Application manual