Forward direction:
Where
X
LLoc
equals line reactance up to the series capacitor(in the picture
approximate 33% of XLine)
X1
Fw
is set to (XLine-X
C
) · p/100.
X1
Rv
= max( 1.5 x (X
C
-X
LLOC
C);
X1
Fw
is defined according to figure 130
When the calculation of X1Fwgives a negative value the zone 1 must
be permanently blocked.
For protection on non compensated lines facing series capacitor on next line. The
setting is thus:
• X1Fw is set to (XLine-XC · K) · p/100.