Mode: The voltage and current used for the power measurement. The setting
possibilities are shown in table 42.
Table 42: Complex power calculation
Set value
Mode
Formula used for complex power calculation
L1, L2, L3
* * *
1 1 2 2 3 3L L L L L L
S U I U I U I= × + × + ×
EQUATION1697 V1 EN (Equation 226)
Arone
* *
1 2 1 2 3 3L L L L L L
S U I U I= × - ×
EQUATION1698 V1 EN (Equation 227)
PosSeq
*
3
PosSeq PosSeq
S U I= × ×
EQUATION1699 V1 EN (Equation 228)
L1L2
* *
1 2 1 2
( )
L L L L
S U I I= × -
EQUATION1700 V1 EN (Equation 229)
L2L3
* *
2 3 2 3
( )
L L L L
S U I I= × -
EQUATION1701 V1 EN (Equation 230)
L3L1
* *
3 1 3 1
( )
L L L L
S U I I= × -
EQUATION1702 V1 EN (Equation 231)
L1
EQUATION1703 V1 EN (Equation 232)
L2
EQUATION1704 V1 EN (Equation 233)
L3
EQUATION1705 V1 EN (Equation 234)
The function has two stages that can be set independently.
With the parameter OpMode1(2) the function can be set On/Off.
The function gives trip if the power component in the direction defined by the setting
Angle1(2) is larger than the set pick up power value Power1(2)
Section 9 1MRK 502 071-UEN -
Current protection
384 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062