EasyManua.ls Logo

ABB REG670 - Page 396

ABB REG670
780 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
en08000358.vsd
IEC08000358 V1 EN
Figure 201: Short-time unbalanced current capability of direct cooled generators
Continuous I
2
- capability of generators is also covered by the standard. Table 44
below (from ANSI standard C50.13) contains the suggested capability:
Table 44: Continous I
2
capability
Type of generator
Permissible I
2
(in percent of rated
generator current)
Salient Pole: with damper winding 10
without damper winding
5
Cylindrical Rotor
Indirectly cooled 10
Directly cooled
to 960 MVA 8
961 to 1200 MVA 6
1201 to 1500 MVA 5
As it is described in the table above that the continuous negative sequence current
capability of the generator is in range of 5% to 10% of the rated generator current.
During an open conductor or open generator breaker pole condition, the negative
sequence current can be in the range of 10% to 30% of the rated generator current.
Other generator or system protections will not usually detect this condition and the
only protection is the negative sequence overcurrent protection.
Negative sequence currents in a generator may be caused by:
Unbalanced loads such as
Single phase railroad load
Unbalanced system faults such as
Section 9 1MRK 502 071-UEN -
Current protection
390 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual

Table of Contents

Other manuals for ABB REG670

Related product manuals