In order to adapt to the previous relay characteristic the above equation can be re-
written in the following way:
[ ]
01
1
1
0
so
s
so
t
K
I
s T
I
I
æ ö
ç ÷
ç ÷
= + ×
ç ÷
æ ö
ç ÷
-
ç ÷
ç ÷
è ø
è ø
EQUATION13000032 V1 EN (Equation 260)
Thus if the following rules are followed when multi-purpose overcurrent stage one is
set:
in >
= I
S0
= 300A
35566
118.55
300
so
A
K
I
= = =
01
0.64B T= =
0.0C =
1.0
p =
1.0k =
then exact replica of the existing relay will be achieved. The following table
summarizes all required settings for the multi-purpose function:
Setting Group1
Operation On
CurrentInput MaxPh
IBase 1000
VoltageInput MaxPh
UBase 20.50
OPerHarmRestr Off
I_2ndI_fund 20.0
BlkLevel2nd 5000
EnRestrainCurr Off
RestrCurrInput PosSeq
RestrCurrCoeff 0.00
RCADir -75
ROADir 75
LowVolt_VM 0.5
Section 13 1MRK 502 071-UEN -
System protection and control
468 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062