NoEvents
OnSet, at pick-up of the signal
OnReset, at drop-out of the signal
OnChange, at both pick-up and drop-out of the signal
AutoDetect, the EVENT function makes the reporting decision (reporting criteria
for integers have no semantic, prefer to be set by the user)
LONChannelMask
or
SPAChannelMask
Definition of which part of the event function block that shall generate events:
Off
Channel 1-8
Channel 9-16
Channel 1-16
MinRepIntVal
(1 - 16)
A time interval between cyclic events can be set individually for each input channel.
This can be set between 0 s to 3600 s in steps of 1 s. It should normally be set to 0, that
is, no cyclic communication.
It is important to set the time interval for cyclic events in an optimized
way to minimize the load on the station bus.
17.6 Disturbance report DRPRDRE
17.6.1 Identification
Function description
IEC 61850 identification IEC 60617
identification
ANSI/IEEE C37.2
device number
Disturbance report DRPRDRE - -
Disturbance report A1RADR - A4RADR - -
Disturbance report B1RBDR - B22RBDR - -
17.6.2 Application
To get fast, complete and reliable information about disturbances in the primary and/
or in the secondary system it is very important to gather information on fault currents,
voltages and events. It is also important having a continuous event-logging to be able
to monitor in an overview perspective. These tasks are accomplished by the
disturbance report function DRPRDRE and facilitate a better understanding of the
power system behavior and related primary and secondary equipment during and after
1MRK 502 071-UEN - Section 17
Monitoring
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 643
Application manual