Control and monitoring functions
GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v15
IEC 61850 or
function name
ANSI Function description Generator
REG670
(Customized)
REG670 (A20)
REG670 (B30)
REG670 (C30)
Control
SESRSYN 25 Synchrocheck, energizing check and synchronizing 0-2 1 2 2
APC30 3 Control functionality for up to 6 bays, max 30 objects (6CBs),
including interlocking (see Table 3)
0-1 1-H39 1-H39 1-H39
QCBAY Bay control 1+5/APC30 1+5/
APC30
1+5/
APC30
1+5/
APC30
LOCREM Handling of LR-switch positions 1+5/APC30 1+5/
APC30
1+5/
APC30
1+5/
APC30
LOCREMCTRL LHMI control of PSTO 1 1 1 1
SXCBR Circuit breaker 18 18 18 18
TCMYLTC 84 Tap changer control and supervision, 6 binary inputs 0-4 1-A31 2-A33 2
TCLYLTC 84 Tap changer control and supervision, 32 binary inputs 0-4
SLGAPC Logic rotating switch for function selection and LHMI presentation 15 15 15 15
VSGAPC Selector mini switch 30 30 30 30
DPGAPC Generic communication function for Double Point indication 16 16 16 16
SPC8GAPC Single point generic control function 8 signals 5 5 5 5
AUTOBITS Automation bits, command function for DNP3.0 3 3 3 3
SINGLECMD Single command, 16 signals 4 4 4 4
I103CMD Function commands for IEC 60870-5-103 1 1 1 1
I103GENCMD Function commands generic for IEC 60870-5-103 50 50 50 50
I103POSCMD IED commands with position and select for IEC 60870-5-103 50 50 50 50
I103POSCMDV IED direct commands with position for IEC 60870-5-103 50 50 50 50
I103IEDCMD IED commands for IEC 60870-5-103 1 1 1 1
I103USRCMD Function commands user defined for IEC 60870-5-103 4 4 4 4
Secondary system
supervision
CCSSPVC 87 Current circuit supervision 0-5 4 5 5
FUFSPVC Fuse failure supervision 0-3 2 3 3
VDSPVC 60 Fuse failure supervision based on voltage difference 0-2 1-G03 1-G03 1-G03
Logic
SMPPTRC 94 Tripping logic 12 12 12 12
SMAGAPC General start matrix block 12 12 12 12
STARTCOMB Start combinator 32 32 32 32
TMAGAPC Trip matrix logic 12 12 12 12
ALMCALH Logic for group alarm 5 5 5 5
1MRK 502 074-BEN A
Generator protection REG670 2.2 and Injection equipment REX060,
REX061, REX062
Product version: 2.2.1
ABB 11