EasyManua.ls Logo

ABB REG670 - Section 10 Diagnose IED status; 10.1 Read internal events; 10.2 Find available functions

ABB REG670
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 33. Insulation tests, REX061
Test Type test values Reference standard
Dielectric test 7.48 kV DC, 1min
(connections to rotor)
2.8 kV DC, 1 min
IEEE 421.3
IEC 60255-27
Impulse voltage test 12.0 kV, 1.2/50 µs, 0.5 J
(connections to rotor)
5.0 kV, 1.2/50 µs, 0.5 J
IEC 60664-1
IEC 60255-27
Insulation resistance >100 MΩ at 500V DC IEC 60255-27
Table 34. Mechanical tests
Test
Reference standards Requirements
Vibration response test IEC 60255-21-1 Class 2
Vibration endurance test
REG670 and REX060
REX061 and REX062
IEC 60255-21-1
Class 1
Class 2
Shock response test
REG670 and REX060
REX061 and REX062
IEC 60255-21-2
Class 1
Class 2
Shock withstand test
REG670 and REX060
REX061 and REX062
IEC 60255-21-2
Class 1
Class 2
Bump test
REG670 and REX060
REX061 and REX062
IEC 60255-21-2
Class 1
Class 2
Seismic test
REG670 and REX060
REX061 and REX062
IEC 60255-21-3
Class 2
Class 2 extended
Table 35. Environmental tests
Test
Type test value Reference standard
Cold test
operation
storage
16 h at -25°C
16 h at -40°C
IEC 60068-2-1
Dry heat test
operation
storage
16 h at +70°C
16 h at +85°C
IEC 60068-2-2
Damp heat test
steady state
cyclic
240 h at +40ºC
humidity 93%
6 cycles at +25 to +55ºC
humidity 93-95%
IEC 60068-2-78
IEC 60068-2-30
1MRK 502 074-BEN A
Generator protection REG670 2.2 and Injection equipment REX060,
REX061, REX062
Product version: 2.2.1
ABB 59

Other manuals for ABB REG670

Related product manuals