Differential protection
SEMOD175004-2 v10
Table 39. Generator differential protection GENPDIF
Function Range or value Accuracy
Unrestrained differential current limit (1-50)p.u. of
IBase
±1.0% of set value
Reset ratio > 95% -
Minimum pickup (0.05–1.00)p.u. of
IBase
±1.0% of I
r
Negative sequence current level (0.02–0.20)p.u. of
IBase
±1.0% of I
r
Operate time at 0 to 2 x IdMin
restrained function
Min. = 25 ms
Max. = 35 ms
-
Reset time at 2 x IdMin to 0
restrained function
Min. = 10 ms
Max. = 25 ms
-
Operate time at 0 to 5 x IdUnre
unrestrained function
Min. = 5 ms
Max. = 15 ms
-
Reset time at 5 x IdUnre to 0
unrestrained function
Min. = 15 ms
Max. = 30 ms
-
Critical impulse time, unrestrained
function
2 ms typically at 0 to 5 x IdUnre -
Impulse margin time unrestrained function 10 ms typically -
Operate time at 0 to 5 x IMinNegSeq
Negative sequence unrestrained function
Min. = 25 ms
Max. = 35 ms
-
Reset time at 5 x IMinNegSeq to 0
Negative sequence unrestrained function
Min. = 30 ms
Max. = 45 ms
-
1MRK 502 074-BEN A
Generator protection REG670 2.2 and Injection equipment REX060,
REX061, REX062
Product version: 2.2.1
ABB 61