IEC140000134-1-en.vsd
IEC140000134 V1 EN-US
1.1. Navigate to the Settings tab.
1.2. Force the IP stack to IPv4 by setting the parameter ForceIPv4 to True.
2. Set the Connection Parameters on PMU Connection Tester for TCP
communication according to the PMU configuration.
IEC140000135-1-en.vsd
IEC140000135 V1 EN-US
Section 11 1MRK 502 073-UUS A
Establishing connection and verifying the IEEE C37.118/1344 communication
112 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Commissioning manual