communication explains how to set the PMU Connection Tester parameters in order to
establish an IEEE C37.118 connection with the PMU.
11.5.1 Verifying the IEEE C37.118/1344 TCP communication
GUID-289E2E92-431E-45FE-B586-A723588B98A1 v1
After setting both PMU configuration and the TCP client configuration (As explained
in sections
Setting the PMU station communication (PMU Report), Setting the PMU
station communication (PMU configuration) and Setting the TCP/UDP client
communication) and making sure that the Ethernet communication is set up, click
Connect on the PMU Connection Tester tool.
IEC140000138 V1 EN-US
Figure 30: Verifying the TCP communication using PMU Connection Tester
• Now it should be possible to see the streaming synchrophasor data. In the Graph
tab, observe the Frequency, data Reporting Rate, Phasor names, and Phase angles
of the reported synchrophasors. Observe the real-time frame details of the Data
Frame in the bottom of the window.
1MRK 502 073-UUS A Section 11
Establishing connection and verifying the IEEE C37.118/1344 communication
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 115
Commissioning manual