Verifying the settings by secondary injection
GUID-1752CE04-7C0F-4D37-9602-B22D8096DD2D v1
It is advised to connect the analog output channels of the function block OOSPPAM to
the internal disturbance recorder (and in particular to the function block A4RADR) in
order to perform a better analysis of the tests.
If the device is in test mode, the recording of the disturbances are enabled by the
setting in Main menu/Settings/IED Settings/Monitoring/Disturbance report/
DisturbanceReport/DRPRDRE:1: set the parameter OpModeTest to On.
1. Check the Application Configuration: verify that hardware voltage and current
channels of the IED are properly connected to SMAI function blocks, and that the
proper analog outputs of SMAI’s are connected to the analog inputs of the function
block OOSPPAM.
2. Connect three-phase voltage channels of the test set to the appropriate IED
terminals.
3. Connect in parallel two groups of three-phase currents of the test set to the
appropriate IED terminals.
4. Connect the appropriate trip output of the IED to the input channel of the test set
that monitors the trip.
5. Go to Main menu/Settings/IED Settings/Impedance protection/
OutOfStep(78,Ucos)/OOSPPAM(78,Ucos):1, and make sure that the function is
enabled, that is, Operation is set to On.
13.4.5.2 Test of point RE (R
FwdR
, X
FwdX
)
GUID-911D370F-8767-4D6C-9621-8663DD26006C v1
The trajectory of the impedance does not enter the lens characteristic.
GUID-5C5E9BEB-AA60-474E-ACEC-B972ACFE6FA2 v1
Preliminary steady state test at 50 Hz
GUID-8F95CCCC-3282-48E8-9F5E-3F3E77CCCAAE v1
• Go to Main menu/Test/Function status/Impedance protection/
OutOfStep(78,Ucos)/OOSPPAM(78,Ucos):1/Outputs to check the available
service values of the function block OOSPPAM.
• Apply the following three-phase symmetrical quantities (the phase angle is related
to phase L1):
V V
V
V
V
ts t FwdZ
VT s
VT p
= × × = × × =1 1 1 1 11931
0 1
13 8
95 1. .
.
.
.
,
,
,
EQUATION14057 V1 EN-US (Equation 17)
∠ =
=
=V
ForwardX
ForwardR
ts
arctan arctan
.
.
59 33
8 19
82..14°
EQUATION14058 V1 EN-US (Equation 18)
frequency of V
ts
= 50 Hz
1MRK 502 073-UUS A Section 13
Testing functionality by secondary injection
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 165
Commissioning manual