Figure 49: Boolean output signals for the injected current with two components: a
50 Hz current component and a 49.5 Hz current component
13.4.6 Loss of excitation LEXPDIS (40)
SEMOD158873-3 v3
Prepare the IED for verification of settings outlined in Section "Preparing the IED to
verify settings".
13.4.6.1 Verifying the settings
SEMOD158873-39 v3
The test is done by means of injection of three phase current and three phase voltage
from a modern test device. This test device shall be able to give voltage and current
corresponding to the set apparent impedance.
1. Feed the IED with current and voltage corresponding to the apparent impedance:
Test #1, as shown in figure
50. Read the analog outputs for R and X and check
1MRK 502 073-UUS A Section 13
Testing functionality by secondary injection
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 179
Commissioning manual