13.11 Logic
SEMOD53577-1 v1
13.11.1 Tripping logic, common 3-phase output SMPPTRC (94)
SEMOD54375-102 v10
Prepare the IED for verification of settings outlined in Section "Preparing the IED to
verify settings".
This function is functionality tested together with other protection functions (line
differential protection, ground-fault overcurrent protection, and so on) within the IED.
It is recommended that the function is tested together with the autorecloser function,
when built into the IED or when a separate external unit is used for reclosing purposes.
13.11.1.1 3 phase operating mode
SEMOD54375-106 v10
1. Check that AutoLock and TripLockout are both set to Disabled.
2. Initiate a three-phase fault.
An adequate time interval between the faults should be considered, to overcome a
reset time caused by the possible activation of the autorecloser function
SMBRREC (79). The function must issue a three-pole trip in all cases when trip
is initiated by any protection or some other built-in or external function. The
following functional output signals must always appear simultaneously: TRIP,
TR_A, TR_B, TR_C and TR3P.
13.11.1.2 1p/3p operating mode
SEMOD54375-116 v5
In addition to various other tests, the following tests should be performed. They depend
on the complete configuration of an IED:
Procedure
1. Make sure that TripLockout and AutoLock are both set to Disabled.
2. Initiate different single-phase-to-ground faults one at a time.
3. Initiate different phase-to-phase and three-phase faults.
Consider using an adequate time interval between faults, to overcome a reset
time, which is activated by SMBRREC (79). A three-pole trip should occur for
each separate fault and all of the trips. Functional outputs TRIP, all TR_A, TR_B,
TR_C and TR3P should be active at each fault.
Section 13 1MRK 502 073-UUS A
Testing functionality by secondary injection
270 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Commissioning manual