4.5 Energizing REX060
4.5.1 REX060 start up sequence
GUID-63A15CD3-17B0-41DD-9611-8272DDA53137 v1
When the injection unit REX060 is energized, the ABB logotype is shown followed by
current REX060 revision status. When the start up sequence is completed, the main
menu (normal display content) is shown. The duration of the start up sequence is a few
seconds.
4.6 Setting up communication between PCM600 and the
IED
SEMOD58570-5 v14
The communication between the IED and PCM600 is independent of the
communication protocol used within the substation or to the NCC.
The communication media is always Ethernet and the used transport layer is TCP/IP.
Each IED has an RJ-45 Ethernet interface connector on the front. The front Ethernet
connector is recommended to be used for communication with PCM600.
When an Ethernet-based station protocol is used, PCM600 communication can use the
same Ethernet port and IP address.
To connect PCM600 to the IED, two basic variants must be considered.
• Direct point-to-point link between PCM600 and the IED front port. The front port
can be seen as a service port.
• A link via a station LAN or from remote via a network.
The physical connection and the IP address must be configured in both cases to enable
communication.
The communication procedures are the same in both cases.
1. If needed, set the IP address for the IEDs.
2. Set up the PC or workstation for a direct link (point-to-point), or
3. Connect the PC or workstation to the LAN/WAN network.
4. Configure the IED IP addresses in the PCM600 project for each IED to match the
IP addresses of the physical IEDs.
Section 4 1MRK 502 073-UUS A
Starting up
48 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Commissioning manual