EasyManua.ls Logo

ABB REJ603 - Page 9

ABB REJ603
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Self-powered feeder protection
1MDB07217-YN
REJ603
Product version: 3.0
Issued: 2017-11-21
Revision: E
9 ABB
Table 12. Environmental conditions
Description
Value
Operating temperature range
-25...+55ºC
Short-time service temperature range
-40...+85ºC (<16 h)
Display viewable range : above -20 ºC up to
+70 ºC
Relative humidity
< 93%, non-condensing
Atmospheric pressure
86...106 kPa
Altitude
up to 2000 m
Transport and storage temperature range
-40...+85ºC
Table 13. Environmental tests
Description
Type test value
Reference
Dry heat test (humidity < 50% )
Working
Storing
96 h at +70°C
96 h at +85°C
IEC 60068-2-2
Dry cold test
Working
Storing
96 h at -25°C
96 h at -40°C
IEC 60068-2-1
Damp heat test, cyclic
2 cycles (12 h + 12 h) at
+25°C…+55°C,
Rh > 93%
IEC 60068-2-30
Change of temperature test
Cyclic : 3 hours at -25°C + 3
hours at +55°C ,
Number of cycles : 5
IEC 60068-2-14
Table 14. Electromagnetic compatibility tests
Description
Type test value
Reference
1 MHz/100 kHz burst disturbance test:
Common mode
Differential mode
2.5 kV, 400/40 pulses/s
1.0 kV, 400/40 pulses/s
IEC 61000-4-18, class III
IEC 60255-26
Electrostatic discharge test:
Contact discharge
Air discharge
4 kV, 150 pF/330 Ω
6 kV, 150 pF/330 Ω
IEC 61000-4-2
Conducted radio frequency interference
tests:
10 V
f=150 KHz...80 Mhz
10 V
f=27, 68 MHz
Not applicable for low energy trip
output
IEC 60255-26
IEC 61000-4-6