HMI module LED indications &KDSWHU
8QGHUVWDQGWKH+XPDQ0DFKLQH
,QWHUIDFH
+0,PRGXOH/('LQGLFDWLRQV
The LEDs above the LCD indicates the terminal’s status.
)LJXUH ([DPSOHRIWKH+0,PRGXOH
7DEOH /('LQGLFDWLRQV
'LVSOD\ 0HDQV
Off (no LED is lit) No power or defect terminal.
Steady green LED The terminal is ready for operation.
Flashing green LED Internal failure, startup is in progress
Flashing yellow LED Terminal in test mode.
Steady yellow LED Disturbance report trigged.
Steady red LED A binary signal, normally a TRIP command, has
been activated. Which binary signal(s) that are
supposed to activate the red LED is defined in
the disturbance report.
Flashing red LED Terminal blocked or in configuration mode.
en00000422.vsd
E
C
5HDG\
5([[[9HU;;
& 4XLW
( (QWHUPHQX
6WDUW 7ULS
Push buttons
green yellow red
LEDs
Liquid Crystal Display
four rows
16 characters/row
Optical connector
for local PC