If the terminal is connected to a monitoring or control system via the rear SPA/IEC port,
the SPA/IEC port has to be set either for SPA or IEC use.
 (QWHULQJ63$VHWWLQJV
When using the IEC protocol, the rear SPA/IEC port must be set for IEC use.
The SPA/IEC port is located at terminal X13 on the rear side of the terminal. Only op-
tical fibres, plastic fibres with connector of type HFBR or glass fibres with connectors
of type ST can be used.
3URFHGXUH
 6HWWKHRSHUDWLRQRIWKHUHDU63$,(&SRUWWR³63$´
The operation of the rear SPA/IEC port can be found on the local
HMI at:
&RQILJXUDWLRQ7HUPLQDO&RP63$,(&3RUW
 6ZLWFKWKHWHUPLQDORIIDQGRQ
Now the SPA/IEC port operates as a SPA port.
 6HWWKHVODYHQXPEHUDQGEDXGUDWHIRUWKHUHDU63$SRUW
The slave number and baud rate can be found on the local HMI at:
&RQILJXUDWLRQ7HUPLQDO&RP63$&RP5HDU
Set the same slave number and baud rate as set in the SMS system
for the terminal.
 (QWHULQJ,(&VHWWLQJV
When using the IEC protocol, the rear SPA/IEC port must be set for IEC use.
The SPA/IEC port is located at terminal X13 on the rear side of the terminal. Only op-
tical fibres, plastic fibres with connector of type HFBR or glass fibres with connectors
of type ST can be used.