99
Disturbance report (DRP) Chapter 8
Monitoring
Table 110: Current parameters for disturbance recorder
Table 111: Disturbance report settings
1.6 Technical data
Table 112: DRP - Disturbance report setting performance
Parameter Range Default Unit Description
Operation Off, On On - Determines if the analog signal is to be
recorded (on) or not (off).
<TrigLevel 0-200
Step: 1
50 % of Inb Undercurrent trigger level in per cent of
signal.
>TrigLevel 0-5000
Step: 1
200 % of Inb Overcurrent trigger level in per cent of
signal.
<TrigOperation Off, On Off - Determines if the analog signal’s under-
current trigger condition should be used
(on) or not (off)
>TrigOperation Off, On Off - Determines if the analog signal’s overcur-
rent trigger condition should be used (on)
or not (off)
Operation DisturbSum-
mary
Then the results are...
Off Off • Disturbances are not stored.
• LED information is not displayed on the HMI and not stored.
• No disturbance summary is scrolled on the HMI.
Off On • Disturbances are not stored.
• LED information (yellow - start, red - trip) are displayed on the local
HMI but not stored in the terminal.
• Disturbance summary is scrolled automatically on the local HMI for the
two latest recorded disturbances, until cleared.
• The information is not stored in the terminal.
On On or Off • The disturbance report works as in normal mode.
• Disturbances are stored. Data can be read from the local HMI, a
front-connected PC, or SMS.- LED information (yellow - start, red - trip)
is stored.
• The disturbance summary is scrolled automatically on the local HMI for
the two latest recorded disturbances, until cleared.
• All disturbance data that is stored during test mode remains in the ter-
minal when changing back to normal mode.
Data Setting range
Pre-fault time, tPre 50-300 ms in steps of 10 ms
Post-fault time, tPost 100-5000 ms in steps of 100 ms
Limit time, tLim 500-6000 ms in steps of 100 ms
Number of recorded disturbances Max. 10