Terminal identification rated and base values Chapter 2
General
Path in local HMI: Configuration/AnalogInputs/I1-I5
Table 9: Analog Inputs - Current
Path in local HMI: Configuration/AnalogInputs/U, I, P, Q, S, f
Table 10: Labels for service values
Parameter Range Default Unit Description
I1b 0.1 - 10.0
Step: 0.1
1.0 A Base current of input I1
I1Scale 1.000 -
40000.000
Step: 0.001
2000.000 - Main current transformer ratio, input
I1
Name_I1 0 - 13 I1 char User-defined name of input I1
I2b 0.1 - 10.0
Step: 0.1
1.0 A Base current of input I2
I2Scale 1.000 -
40000.000
Step:0.001
2000.000 - Main current transformer ratio, input
I2
Name_I2 0 - 13 I2 char User-defined name of input I2
I3b 0.1 - 10.0
Step: 0.1
1.0 A Base current of input I3
I3Scale 1.000 -
40000.000
Step: 0.001
2000.000 - Main current transformer ratio, input
I3
Name_I3 0 - 13 I3 char User-defined name of input I3
I4b 0.1 - 10.0
Step: 0.1
1.0 A Base current of input I4
I4Scale 1.000 -
40000.000
Step: 0.001
2000.000 - Main current transformer ratio, input
I4
Name_I4 0 - 13 I4 char User-defined name of input I4
I5b 0.1 - 10.0
Step: 0.1
1.0 A Base current of input I5
I5Scale 1.000 -
40000.000
Step: 0.001
2000.000 - Main current transformer ratio, input
I5
Name_I5 0 - 13 I5 char User-defined name of input I5