52
Configurable logic blocks (CL1) Chapter 3
Common functions
Table 63: Output signals for the TS (TSnn-) function block
6.13.1 Setting parameters
Path in local HMI: Settings/Functions/Group1/TimerSet1/TimerSetnn
Table 64: Setting parameters for the TS (TSn-) function
6.14 Technical data
Table 65: CL1 - Configurable blocks as basic
Table 66: Available timer function blocks as basic
Signal Description
ON Output from timer, pick-up delayed
OFF Output from timer, drop-out delayed
Parameter Range Default Unit Description
Operation Off/On Off - Operating mode for TSn function
T 0.00-60.00
Step: 0.01
0.00 s Delay for settable timer n
Update rate Block Availability
10 ms AND 30 gates
OR 60 gates
INV 20 inverters
SM 5 flip-flops
GT 5 gates
TS 5 timers
200 ms SR 5 flip-flops
XOR 39 gates
Block Availability Setting range Accuracy
TM 10 timers 0.000-60.000 s in steps
of 1 ms
± 0.5% ± 10 ms
TP 10 pulse timers 0.000-60.000 s in steps
of 1 ms
± 0.5% ± 10 ms
TL 10 timers 0.0-90000.0 s in steps of
0.1 s
± 0.5% ± 10 ms
TQ 10 puls timers 0.0-90000.0 s in steps of
0.1 s
± 0.5% ± 10 ms