EasyManua.ls Logo

ABB REL650 - Page 179

ABB REL650
516 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A fault in C has to be applied, and then the maximum current seen from the IED (I
M
) on
the healthy line (this applies for single-phase-to-ground and two-phase-to-ground faults)
is calculated.
~ ~
Z
A
Z
B
Z
L1
A B
I
M
Fault
IED
Z
L2
M
C
Line 1
Line 2
ANSI09000025_2_en.vsd
ANSI09000025 V2 EN
Figure 81: Two parallel lines. Influence from parallel line to the through fault current:
I
M
The minimum theoretical current setting for the overcurrent protection function (Imin)
will be:
Imin MAX I
fA
I
fB
I
M
, ,( )³
EQUATION82 V1 EN
(Equation 97)
Where I
fA
and I
fB
have been described in the previous paragraph. Considering the safety
margins mentioned previously, the minimum setting (Is) for the instantaneous phase
overcurrent protection 3-phase output is then:
Is
³1.3·Imin
EQUATION83 V2 EN (Equation 98)
The protection function can be used for the specific application only if this setting value
is equal or less than the maximum phase fault current that the IED has to clear.
The IED setting value Pickup is given in percentage of the primary base current value,
IBase. The value for Pickup is given from this formula:
100
Is
Pickup
IBase
= ×
ANSIEQUATION1147 V1 EN (Equation 99)
1MRK 506 334-UUS A Section 7
Current protection
173
Application manual

Table of Contents

Other manuals for ABB REL650

Related product manuals