EasyManua.ls Logo

ABB REL650 - Setting Guidelines

ABB REL650
516 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16.6 Setting guidelines
The redundant station bus communication is configured using the local HMI, Main
Menu/Configuration/Communication/TCP-IP configuation/ETHLAN1_AB
The settings can be viewed and OperationMode can be set in the Parameter Setting tool in
PCM600 under IED Configuration/Communication/TCP-IP configuration/
ETHLAN1_AB where
OperationMode can be set to Off, NonRedundant(A) or PRP(A+B). The redundant
communication will be activated when this parameter is set to PRP(A+B).
The ETHLAN1_AB in the Parameter Setting tool is relevant only when the COM03
module is present.
IEC13000009-1-en.vsd
IEC13000009 V1 EN
Figure 221: PRP1 Configured in the Parameter Setting tool
IEC13000010-1-en.vsd
IEC13000010 V1 EN
Figure 222: Lock/Unlock parameter
1MRK 506 334-UUS A Section 16
Station communication
467
Application manual

Table of Contents

Other manuals for ABB REL650

Related product manuals