Figure 20: Thermal overload and circuit-breaker failure protection
The thermal overload protection T1PTTR1 provides indication on overload
situations. LED 4 is used for the thermal overload protection alarm indication.
The circuit-breaker failure protection CCBRBRF1 is initiated via the start input by a
number of different protection stages in the protection relay. The circuit-breaker
failure protection function offers different operating modes associated with the circuit
breaker position and the measured phase and residual currents. The breaker failure
protection has two operating outputs: TRRET and TRBU. The TRRET operate output
is used for retripping its own breaker through the Master Trip 2. TRBU output is used
to give a backup trip to the circuit breaker feeding upstream. For this purpose, the
TRBU operate output signal is connected to the output PO2 (X100:8-9). LED 8 is used
for backup (TRBU) operate indication.