EasyManua.ls Logo

ABB Relion 611 Series - Page 48

ABB Relion 611 Series
188 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
X120-BI2
X100 PO2
LED 8
PHIPTOC1_OPERATE
PHHPTOC2_OPERATE
PHLPTOC1_OPERATE
PHHPTOC1_OPERATE
DEFHPTOC1_OPERATE
OR
DEFLPTOC1_OPERATE
DEFLPTOC2_OPERATE
SELGAPC3
OUT_2IN_4
OSWGAPC15
OUTIN_5
LED 4
THERMAL OVERLOAD PROTECTION
CIRCUIT BREAKER FAILURE PROTECTION
SELGAPC4
OUT_8
IN_17
OSWGAPC11
OUT
IN_1
SELGAPC4
OUT_4
IN_13
SELGAPC1
OUT_2IN_2
CB Closed Position
51BF/51NBF(1)
3I
Io
START
TRRET
TRBU
POSCLOSE
CB_FAULT
BLOCK
CB_FAULT_AL
CCBRBRF1
3I>/Io>BF(1)
T1PTTR1
3Ith>F(1)
49F(1)
BLK_OPR
START
OPERATE3I
BLK_CLOSE
ALARMENA_MULT
AMB_TEMP
GUID-A046A312-1E3B-4186-BBEB-2AF8C2423C5F V1 EN
Figure 20: Thermal overload and circuit-breaker failure protection
The thermal overload protection T1PTTR1 provides indication on overload
situations. LED 4 is used for the thermal overload protection alarm indication.
The circuit-breaker failure protection CCBRBRF1 is initiated via the start input by a
number of different protection stages in the protection relay. The circuit-breaker
failure protection function offers different operating modes associated with the circuit
breaker position and the measured phase and residual currents. The breaker failure
protection has two operating outputs: TRRET and TRBU. The TRRET operate output
is used for retripping its own breaker through the Master Trip 2. TRBU output is used
to give a backup trip to the circuit breaker feeding upstream. For this purpose, the
TRBU operate output signal is connected to the output PO2 (X100:8-9). LED 8 is used
for backup (TRBU) operate indication.
Section 3 1MRS757456 D
REF611 standardized configurations
42 REF611
Application Manual