GUID-CC7AF316-6030-4959-B6EE-032E6415804C V1 EN
Figure 34: ISWGAPC3
ISWGAPC4
ISWGAPC4 input is used to configure which protection function is blocked by the
autoreclosing function by changing the ISWGAPC4 parameters. ISWGAPC4 input is
routed from DARREC1 output PROT_CRD. ISWGAPC4 outputs are connected to the
BLOCK inputs of some of the protection functions.
GUID-E0106013-2B27-4DED-81C7-40ED4F0A94F0 V1 EN
Figure 35: ISWGAPC4
SELGAPC2
SELGAPC2 inputs represent the circuit breaker closed and open position from
SELGACP1. SELGAPC2 outputs are routed to the BLOCK input of the trip circuit
supervision TCSSCBR1 and TCSSCBR2.
By default, X100 PO3 and PO4 are both used for the open circuit breaker. TCSSCBR1
and TCSSCBR2 are both blocked by the circuit breaker open position. If X100-PO3
is used for closing the circuit breaker, TCSSCBR1 needs to be blocked by circuit
breaker close position (OUT_1 connection=IN_1). If X100-PO4 is used for closing
Section 3 1MRS757456 D
REF611 standardized configurations
56 REF611
Application Manual