The mode of all logical nodes located under CTRL logical device are set with Control
mode. Control mode is selected via the HMI or PCM600 path Configuration/Control/
General. By default, Control mode can only be set locally through LHMI.Control mode
inherits its value from Test mode but Control mode ”On”, “Blocked” and “Off” can also
be independently set. Control mode is also available via IEC 61850 communication
(CTRL.LLN0.Mod).
Table 9: Control mode
Control mode Description Control BEH_BLK
On Normal operation FALSE
Blocked Control function commands blocked TRUE
Off Control functions disabled FALSE
According to IEC 61850, the physical outputs to process should be blocked when device
is set to blocked or test blocked mode. The usage depends heavily on the actual ACT
configuration. In the protection blocking example the main trip from TRPPTRC1 is
blocked, and in the control blocking example the CBXCBR1 is blocked. Both comply to
the IEC 61850. In real applications some of PTRC’s might also be used for signalling
purposes (GOOSE) and blocking and interlocking via IO.
5.7.1 Protection blocking example
The physical outputs to process can be blocked with “IED blocked” and “IED test and
blocked” modes. If physical outputs need to be blocked, the application configuration
must block signals or function blocks that affect primary apparatuses. Blocking scheme
needs to use the BEH_BLK output of the PROTECTION function block.
TRPPTRC1
BLOCK
OPERATE
RST_LKOUT
TRIP
CL_LKOUT
Protection
BI_SG_2
BI_SG_3
BI_SG_4
BI_SG_5
BI_SG_6
SG_LOGIC_SEL
SG_1_ACT
SG_2_ACT
SG_3_ACT
SG_4_ACT
SG_5_ACT
SG_6_ACT
BEH_TEST
BEH_BLK
TRPPTRC1_TRIP
GUID-CAF67CB2-774E-4122-A235-D07F8768B202 V1 EN
Figure 67: Master trip TRPPTRC blocked using Protection function block
BEH_BLK
output
1MAC108982-MB E Section 5
Protection and control engineering
615 series ANSI 103
Engineering Manual