5.7.2 Control blocking example
The physical outputs to process can be blocked with “Blocked” mode. If physical outputs
need to be blocked, the application configuration must block signals or function blocks
that affect primary apparatuses. Blocking scheme needs to use BEH_BLK output of
CONTROL function block.