Function IEC 61850 Logical device Logical nodes in
Ver.5.0 FP1
Logical nodes in
Ver.4.2 or older
Three-phase directional overcurrent protection, high stage DPHHPDOC LD0 DPHHPTOC
DPHHRDIR
DPHHPTOC
DPHHRDIR
Three-phase voltage-dependent overcurrent protection PHPVOC LD0 PHPVOC
Non-directional ground-fault protection, low stage EFLPTOC LD0 EFLPTOC EFLPTOC
Non-directional ground-fault protection, high stage EFHPTOC LD0 EFHPTOC EFHPTOC
Non-directional ground-fault protection, instantaneous stage EFIPTOC LD0 EFIPTOC EFIPTOC
Directional ground-fault protection, low stage DEFLPDEF LD0 DEFLPTOC
DEFLRDIR
DEFLPTOC
DEFLRDIR
Directional ground-fault protection, high stage DEFHPDEF LD0 DEFHPTOC
DEFHRDIR
DEFHPTOC
DEFHRDIR
Admittance-based ground-fault protection EFPADM LD0 EFPADM EFPADM
Wattmetric-based ground-fault protection WPWDE LD0 WRDIR
WPSDE
WMMXU
WRDIR
WPSDE
WMMXU
Transient/intermittent ground-fault protection
INTRPTEF LD0 INTRPTEF INTRPTEF
Harmonics-based ground-fault protection HAEFPTOC LD0 HAEFPTOC
HAEFMHAI
HAEFPTOC
HAEFMHAI
Non-directional (cross-country) ground-fault protection,
using calculated Io
EFHPTOC LD0 EFHPTOC EFHPTOC
Negative-sequence overcurrent protection NSPTOC LD0 NSPTOC NSPTOC
Phase discontinuity protection PDNSPTOC LD0 PDNSPTOC PDNSPTOC
Residual overvoltage protection ROVPTOV LD0 ROVPTOV ROVPTOV
Three-phase undervoltage protection PHPTUV LD0 PHPTUV PHPTUV
Three-phase overvoltage protection PHPTOV LD0 PHPTOV PHPTOV
Positive-sequence undervoltage protection PSPTUV LD0 PSPTUV PSPTUV
Negative-sequence overvoltage protection NSPTOV LD0 NSPTOV NSPTOV
Three-phase remnant undervoltage protection MSVPR LD0 MRMMXU
MSVPR
Frequency protection FRPFRQ LD0 FRPTRC
FRPTOF
FRPTUF
FRPFRC
FRPTRC
FRPTOF
FRPTUF
FRPFRC
Overexcitation protection
OEPVPH LD0 OEPVPH
Three-phase thermal protection for feeders, cables and
distribution transformers
T1PTTR LD0 T1PTTR T1PTTR
Three-phase thermal overload protection, two time
constants
T2PTTR LD0 T2PTTR T2PTTR
Negative-sequence overcurrent protection for machines MNSPTOC LD0 MNSPTOC MNSPTOC
Loss of load supervision LOFLPTUC LD0 LOFLPTUC LOFLPTUC
Motor load jam protection JAMPTOC LD0 JAMPTOC JAMPTOC
Table continues on next page
Section 7 1MAC108982-MB E
IEC 61850 communication engineering
126 615 series ANSI