If the IED 61850 configuration engineering mode is enabled, SCD files cannot be
imported and an error message is shown.
GUID-68D1D489-27AC-4729-A887-DCE496CB48E0 V1 EN
Figure 92: Error message when SCD files cannot be imported
7.3.3.1 Importing SCD files
To be able to import an SCD file at station level, the option IED 61850 configuration
engineering mode enabled has to be cleared in PCM600.
1. Select the station in the Plant Structure view.
2. Right-click the station and select Import.
3. From the open standard Windows menu, select the file to be imported and start the
reading.
The SCL Import Options dialog box opens, querying how the file should be
handled during the import.
GUID-ADF60975-2AD7-47CF-AD26-37094ACEA4F0 V1 EN
Figure 93: SCL Import Options
4. In the SCL Import Options dialog box, select how to handle the file during the
import.
Section 7 1MAC108982-MB E
IEC 61850 communication engineering
142 615 series ANSI
Engineering Manual