When a changed configuration is written to the protection relay, the horizontal
communication configuration needs to be updated.
GUID-EEB7D9BD-5D8C-4A18-9A94-848B2821658D V2 EN
Figure 96: Updating the communication configuration in the IED with the
configuration made in PCM600
1. Select which configuration part to include in writing.
• Select GOOSE to update the GOOSE configuration part in the IED.
• Select Process bus (IEC 61850-9-2) to update the IEC 61850-9-2
configuration part in the IED.
2. Select whether or not to update the configuration.
• Click Continue to update the selected communication configuration part(s) in
the IED. The options can be left unselected. In this case, other parts of the
configuration are updated.
• Click Cancel to cancel the whole writing operation.
Section 7 1MAC108982-MB E
IEC 61850 communication engineering
146 615 series ANSI
Engineering Manual