2.1 Monitoring and control system structure
The monitoring and control system for electrical substations contains a number of devices
for various purposes.
The maximum size of a project is 180 devices. However, in order to
maintain good performance and usability of the tool, it is recommended to
divide one big project into multiple smaller PCM600 projects.
IEC08000101.vsd
Bay level
Station level
Station
Communication
Station bus
bay
IED 1
bay
IED 2
bay
IED n-1
bay
IED n
NCC-GW
(station-IED2)
PCM600
(tool set)
HSI
(station-IED1)
GUID-414609A0-5B40-453F-83D4-4551B2894023 V1 EN
Figure 3: Principle structure of a monitoring and control system for a substation
The monitoring and control system can be divided into three main parts.
Bay level devices
Station communication
Station level devices
All three parts require specific engineering and configuration.
A plant structure is used to identify each device in its location within the substation
organization. The plant structure is a logical image of the substation and the bays within
the substation. The organization structure for the devices may differ from the structure of
the primary equipment in the substation.
In PCM600 it is possible to set up a hierarchical structure of five levels for the device
identification.
Section 2 1MAC108982-MB E
Relay engineering process
18 615 series ANSI
Engineering Manual