2.3 Workflow
Make GOOSE connections
Export SCL files from
PCM600
Import SCL files to CCT600
or IET600 and do signal
engineering. Export updated
SCL files from CCT600 or
IET600.
Import SCL files to PCM600
Start
ACT
SMT
PST
GDE
SMT
CMT
ACT
Export
SCD
CCT600
or
IET600
Import
SCD
IED
WRITE
End
Configure IED functionality
Parametrization
Signal engineering
Create single line diagram
for local HMI
Save the work
between the
different steps
Project
Create plant structure and
insert IED objects
IEC 61850
DNP 3.0
Modbus
Write configuration to IED
GUID-400C23DB-E4D5-4DA6-86DB-07BC898E102A V1 EN
Figure 4: Protection relay engineering workflow proposal based on practical
experience and dependencies of the steps
It is possible to follow a different sequence based on the information available at the time
when the project is started. This means that several iterations may be needed to complete
the project.
1MAC108982-MB E Section 2
Relay engineering process
615 series ANSI 21
Engineering Manual