3.6.1 Prerequisites for local and remote updates
Local update
Use of the front port is recommended when updating locally. Remove the IED from
the network especially with redundant network topologies (HSR/PRP).
Remote update
Communication is recommended to be secured either by setting up a VPN connection
or enabling secure communication in the IED via LHMI (Configuration/
Authorization/Remote Update) while updating remotely.
Remote update can be enabled in the IED either via the LHMI (Configuration/
Authorization/Security/Remote Update) or by an administrator in the Parameter
Setting tool in PCM600 (IED Configuration/Configuration/Authorization/
Remote Update to be able to update remotely. If the IED is in local control mode,
remote update proceeds only after a confirmation is received from the user.
Remote update has to be disabled manually after the update, if wanted.
Remote update only works when the IED is connected from the rear port with a
custom IP address.
3.6.2 Updating firmware or language
1. Select the update mode.
Firmware
Language
2. Select the update package and click Next.
Section 3 1MAC108982-MB E
PCM600 tool
40 615 series ANSI
Engineering Manual