• Example: a variable connected to an output signal that is not connected
• Example: if an output from a higher execution order function is connected to
inputs of lower execution order function
• Errors, marked with a red circle with a cross
• Example: unconnected hardware output
Warnings do not prevent writing to the protection relay. However, errors must be
corrected before writing the application configuration to the protection relay. The
application configuration can be saved and the Application Configuration tool can be
closed with open errors, but the application configuration cannot be written to the
protection relay.
These problems are listed in the Output view under the Application Configuration tab.
Double-clicking the error or warning row navigates to the MainApplication/Page/Area,
where the problem was identified.
GUID-F33821B8-2643-4092-85DB-9C732A95C77E V1 EN
Figure 54: Application Configuration tool: validation on demand
5.1.9.3 Validation when writing to the protection relay
When writing the application configuration to the protection relay, an automatic
validation is performed. The validation is the same as the manually demanded validation.
Errors abort the writing.
Section 5 1MAC108982-MB E
Protection and control engineering
86 615 series ANSI
Engineering Manual