RegA Type Scale IEC 61580 name SA name Description Values
2036 i16 1 .AnIn6.mag AI_VAL6 RTD input 6 in ohms -/+ 10000.00
2037 i16 1 .AnIn7.mag AI_VAL7 RTD input 7 in ohms -/+ 10000.00
2038 i16 1 .AnIn8.mag AI_VAL8 RTD input 8 in ohms -/+ 10000.00
2.4.2 Unmapped registers
Unmapped registers are register data that have no initial Modbus mapping locations, but
can be added to the user-definable Modbus area using the Communication Management
tool in PCM600. The initial register type settings of these objects have little meaning,
since it is always possible to redefine the settings completely for the user-definable
register.
2.4.2.1 CTRL.LLN0 Local, Remote, Station, Off and Combinations
Table 170: CTRL.LLN0 Local, Remote, Station, Off and Combinations
RegA Type Scale IEC 61850 name SA name Description Values
CTRL.LLN0
u16 1 .LocKeyHMI.stVal
0=Off; 1=Loc; 2=Rem; 3=Stat;
4=L+R; 5=L+S; 6=L+S+R; 7=S
+R
0…7
2.4.2.2 LD0.LLN0/LPHD1/LDEV1 System values
Table 171: LD0.LLN0/LPHD1/LDEV1 System values
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.LLN0
u16 1 .ParChgCnt.stVal Num. of setting changes 0…65535
2.4.2.3 LD0.MVI4GAPC1 Integer value move (1) – MVI4-1
Table 172: LD0.MVI4GAPC1 Integer value move (1) – MVI4-1
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.MVI4GAPC1
i32 1 .ISCS01.stVal OUT1 - Integer value 1 (high)
-/
+2147483647
- Low word
i32 1 .ISCS02.stVal OUT2 - Integer value 2 (high)
-/
+2147483647
Table continues on next page
1MAC252756-MB B Section 2
Modbus data mappings
REM615 ANSI 95