2.5 Controls
Table 180: Explanations of the controls table columns
Column name
Description
0xA Coil (0X) address for control value.
CS Control structure and bit within the structure for control value.
IEC 61850 name Original IED data object identification. Described in the IEC 61850 format as Logical
Device.Logical Node and thereafter .Data Object.Data Attribute. Logical Node is the
same as the application function block name.
SA name
The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description Short description of the signal. See the technical manual for more information.
Value Meaning of the written value.
2.5.1 Reset, acknowledge and trigger points
Table 181: Reset, acknowledge and trigger points
0xA CS IEC 61850 name SA name Description Values
LD0.LLN0
2060 2.00 .LEDRs1.Oper.ctlVal Reset indications and LEDs 1=Reset
2061 2.01 .LEDRs2.Oper.ctlVal Reset alarm LEDs 1=Reset
LD0.PEMMXU1
2062 2.02 .RecRs.Oper.ctlVal Reset power max demands 1=Reset
2063 2.03 < reserved >
2064 2.04 < reserved >
LD0.SSCBR1
2065 2.05 .RsAccAPwr.Oper.ctlVal Reset CB accum. energy 1=Reset
2066 2.06 .RsCBWear.Oper.ctlVal Reset CB wear data 1=Reset
DR.RDRE1
2067 2.07 .RcdTrg.Oper.ctlVal Trig DR recording 1=Trig
2068 2.08 .MemClr.Oper.ctlVal Clear DR memory 1=Clear
LD0.CMMXU1
2069 2.09 .RecRs.Oper.ctlVal Reset max current1 demands 1=Reset
LD0.PEMMXU1
2070 2.10 .SupDmdRs.Oper.ctlVal Reset energy values 1=Reset
LD0.SCCBR1
2071 2.11 .RsTrvTm.Oper.ctlVal Reset CB travel time 1=Reset
Table continues on next page
1MAC252756-MB B Section 2
Modbus data mappings