2.5.4 CTRL.DCXSWI2 Disconnector control (2) – 29DS-2
Table 184: CTRL.DCXSWI2 Disconnector control (2) – 29DS-2
0xA
CS IEC 61850 name SA name Description Values
CTRL.DCCSWI2
2150 7.06 .Pos.Oper.ctlVal Select open 1=Select
2151 7.07 .Pos.Oper.ctlVal Select close 1=Select
2152 7.08 .Pos.Oper.ctlVal Cancel selection 1=Cancel
2153 7.09 .Pos.Oper.ctlVal Execute selection 1=Execute
2154 7.10 .Pos.Oper.ctlVal Direct open 1=Open
2155 7.11 .Pos.Oper.ctlVal Direct close 1=Close
2.5.5 CTRL.ESXSWI1 Grounding switch control (1) – 29GS-1
Table 185: CTRL.ESXSWI1 Grounding switch control (1) – 29GS-1
0xA CS IEC 61850 name SA name Description Values
CTRL.ESXSWI1
2054 1.06 .Pos.Oper.ctlVal Select open 1=Select
2055 1.07 .Pos.Oper.ctlVal Select close 1=Select
2056 1.08 .Pos.Oper.ctlVal Cancel selection 1=Cancel
2057 1.09 .Pos.Oper.ctlVal Execute selection 1=Execute
2058 1.10 .Pos.Oper.ctlVal Direct open 1=Open
2059 1.11 .Pos.Oper.ctlVal Direct close 1=Close
2.5.6 LD0.LDEV1 Protection relay's warm reset (1)
Table 186: LD0.LDEV1 Protection relay's warm reset (1)
0xA
CS IEC 61850 name SA name Description Values
LD0.LDEV1
2080 3.00 .WrmStrCmd.Oper.ctlVal Warm reboot of protection relay 1=Reboot
2.5.7 LD0.SPCGAPC1 Generic control point (16 pcs) (1) – SPC-1
The binary outputs can be configured either as pulse- or persistent-type outputs. Pulse-
type outputs are triggered with the write value "1". Persistent-type outputs can be written
with both values "1" and "0". The setting mode "toggled" for local operation corresponds
to "persistent" for remote operation.
1MAC252756-MB B Section 2
Modbus data mappings
REM615 ANSI 103
Point List Manual