• Parameter names are shown in italics.
The function can be enabled and disabled with the Operation setting.
• Parameter values are indicated with quotation marks.
The corresponding parameter values are "Enabled" and "Disabled".
• Input/output messages and monitored data names are shown in Courier font.
When the function picks up, the PICKUP output is set to TRUE.
• Dimensions are provided both in inches and mm. If it is not specifically mentioned,
the dimension is in mm.
• This document assumes that the parameter setting visibility is "Advanced".
1.4.3 Functions, codes and symbols
Table 1: Functions included in the relay
Function IEC 61850 IEC 60617 ANSI/C37.2-2008
Protection
Three-phase non-directional overcurrent
protection, low stage
PHLPTOC1 3I> (1) 51P
Three-phase non-directional overcurrent
protection, high stage
PHHPTOC1 3I>> (1) 50P-1
PHHPTOC2 3I>> (2) 50P-2
Three-phase non-directional overcurrent
protection, instantaneous stage
PHIPTOC1 3I>>> (1) 50P-3
Non-directional ground-fault protection, low
stage
EFLPTOC1 Io> (1) 51G
Non-directional ground-fault protection, high
stage
EFHPTOC1 Io>> (1) 50G-1
EFHPTOC2 Io>> (2) 50G-2
Directional ground-fault protection, low stage DEFLPDEF1 Io> -> (1) 67/51N
Residual overvoltage protection ROVPTOV1 Uo> (1) 59G-1
ROVPTOV2 Uo> (2) 59N-1
Three-phase undervoltage protection PHPTUV1 3U< (1) 27-1
PHPTUV2 3U< (2) 27-2
Three-phase overvoltage protection PHPTOV1 3U> (1) 59-1
PHPTOV2 3U> (2) 59-2
Positive-sequence undervoltage protection PSPTUV1 U1< (1) 27PS
Negative-sequence overvoltage protection NSPTOV1 U2> (1) 47-1
NSPTOV2 U2> (2) 47-2
Three-phase remnant undervoltage
protection
MSVPR1 3U< (1) 27R
Frequency protection FRPFRQ1 f>/f<,df/dt (1) 81-1
FRPFRQ2 f>/f<,df/dt (2) 81-2
Table continues on next page
Section 1 1MAC252756-MB B
Introduction
12 REM615 ANSI
Point List Manual