Function IEC 61850 ANSI A B D E
MA01 MA02 MA04 MA05
Time delay off (8 pcs) TOFGAPC 62TOF 4 4 4 4
Time delay on (8 pcs) TONGAPC 62TON 4 4 4 4
Set-reset (8 pcs) SRGAPC SR 4 4 4 4
Move (8 pcs) MVGAPC MV 2 2 2 2
Generic control point (16 pcs) SPCGAPC SPC 2 2 2 2
Analog value scaling SCA4GAPC SCA4 4 4 4 4
Integer value move MVI4GAPC MVI4 1 1 1 1
Generic up-down counters UDFCNT CTR 4 4 4 4
1, 2, ... = Number of included instances. The instances of a protection function represent the number of
identical protection function blocks available in the standard configuration.
() = Optional
1) Master Trip included and connected to corresponding HSO in the configuration only when BIO0007 module
is used. If additionally the ARC option is selected, then AFD is connected in the configuration to the
corresponding Master Trip input.
2) Only available with COM0031...0037
2.3 Indications
Table 3: Explanations of the indications table columns
Column name
Description
BitA Default 0X and 1X bit address for the data.
RegA Default 3X and 4X register.bit (00-15) address for the data.
IEC 61850 name Original IED data object identification. Described in the IEC 61850 format as Logical
Device.Logical Node and thereafter .Data Object.Data Attribute. Logical Node is the
same as the application function block name.
SA name
The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description Short description of the signal. See the technical manual for more information.
Value Meaning of the value states.
Section 2 1MAC252756-MB B
Modbus data mappings
20 REM615 ANSI
Point List Manual