2.3.1 Premapped indications
2.3.1.1 Common data 1
Table 4: Common data 1
BitA
RegA IEC 61850 name SA name Description Values
CTRL.LLN0
2720 170.00 .Loc.stVal - Remote/Local state 0/1=Rem/Loc
2721 170.01 .LocKeyHMI.stVal.Station - Station state 1=Station
DR.RDRE1
2722 170.02 .RcdMade.stVal - DR recording made 1=Made
2723 170.03 .mcd
2.3.1.2 CTRL.CBCILO1 Circuit breaker enable signals (1)
Table 5: CTRL.CBCILO1 Circuit breaker enable signals (1)
BitA RegA IEC 61850 name SA name Description Values
CTRL.CBCILO1
2824 176.08 .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
2825 176.09 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
2.3.1.3 CTRL.CBCSWI1 Circuit breaker (1) mom. position
Table 6: CTRL.CBCSWI1 Circuit breaker (1) mom. position
BitA
RegA IEC 61850 name SA name Description Values
CTRL.CBCSWI1 POSITION
2804 175.04 .Pos.stVal.Close - Close bit 1=Close
2805 175.05 .Pos.stVal.Open - Open bit 1=Open
2806 175.06 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
2834 177.02 .SynItlByps.stVal ITL_BYPASS Interlock bypass 1=Bypass
2835 177.03 .mcd