EasyManua.ls Logo

ABB Relion 615 series - Premapped Indications; Common Data 1; CTRL.CBCILO1 Circuit Breaker Enable Signals (1); CTRL.CBCSWI1 Circuit Breaker (1) Mom. Position

ABB Relion 615 series
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.3.1 Premapped indications
2.3.1.1 Common data 1
Table 4: Common data 1
BitA
RegA IEC 61850 name SA name Description Values
CTRL.LLN0
2720 170.00 .Loc.stVal - Remote/Local state 0/1=Rem/Loc
2721 170.01 .LocKeyHMI.stVal.Station - Station state 1=Station
DR.RDRE1
2722 170.02 .RcdMade.stVal - DR recording made 1=Made
2723 170.03 .mcd
2.3.1.2 CTRL.CBCILO1 Circuit breaker enable signals (1)
Table 5: CTRL.CBCILO1 Circuit breaker enable signals (1)
BitA RegA IEC 61850 name SA name Description Values
CTRL.CBCILO1
2824 176.08 .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
2825 176.09 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
2.3.1.3 CTRL.CBCSWI1 Circuit breaker (1) mom. position
Table 6: CTRL.CBCSWI1 Circuit breaker (1) mom. position
BitA
RegA IEC 61850 name SA name Description Values
CTRL.CBCSWI1 POSITION
2804 175.04 .Pos.stVal.Close - Close bit 1=Close
2805 175.05 .Pos.stVal.Open - Open bit 1=Open
2806 175.06 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
2834 177.02 .SynItlByps.stVal ITL_BYPASS Interlock bypass 1=Bypass
2835 177.03 .mcd
1MAC252756-MB B Section 2
Modbus data mappings
REM615 ANSI 21
Point List Manual

Table of Contents

Other manuals for ABB Relion 615 series