2.3.1.4 CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position
Table 7: CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position
BitA
RegA IEC 61850 name SA name Description Values
CTRL.CBCSWI1 POSITION
2816 176.00 .Pos.stVal.Close Close bit 1=Close
2817 176.01 .mcd
2818 176.02 .Pos.stVal.Open Open bit 1=Open
2819 176.03 .mcd
2820 176.04 < reserved >
2821 176.05 < reserved >
2822 176.06 .Pos.stSeld SELECTED CB selected for control 1=Selected
2823 176.07 .mcd
2.3.1.5 CTRL.CBXCBR1 Circuit-breaker control (1) – 52-1
Table 8: CTRL.CBXCBR1 Circuit-breaker control (1) – 52-1
BitA RegA IEC 61850 name SA name Description Values
CTRL.CBXCBR1
2836 177.04 .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
2837 177.05 .mcd
2838 177.06 .BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
2839 177.07 .mcd
2840 177.08 .ItlByPss.stVal ITL_BYPASS Interlock bypass 1=Bypass
2841 177.09 .mcd
2.3.1.6 CTRL.DCSXSWI1 Disconnector position indication (1) – 52-TOC
Table 9: CTRL.DCSXSWI1 Disconnector position indication (1) – 52-TOC
BitA
RegA IEC 61850 name SA name Description Values
CTRL.DCSXSWI1 POSITION
2792 174.08 .Pos.stVal.Close - Close bit 1=Close
2793 174.09 .Pos.stVal.Open - Open bit 1=Open
2794 174.10 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
Section 2 1MAC252756-MB B