2.3.1.10 CTRL.DCXSWI2 Disconnector control (2) – 29DS-2
Table 13: CTRL.DCXSWI2 Disconnector control (2) – 29DS-2
BitA
RegA IEC 61850 name SA name Description Values
CTRL.DCXSWI2 POSITION
3484 217.12 .Pos.stVal.Close - Close bit 1=Close
3485 217.13 .Pos.stVal.Open - Open bit 1=Open
3486 217.14 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
3487 217.15 .Pos.stSeld - Control selected 1=Selected
CTRL.DCCILO2
3488 218.00 .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
3489 218.01 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
CTRL.DCXSWI2
3490 218.02 .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
3491 218.03 .mcd
3492 218.04 .BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
3493 218.05 .mcd
CTRL.DCCILO2
3494 218.06 .ItlByps.stVal ITL_BYPASS Interlock bypass 1=Bypass
3495 218.07 .mcd
2.3.1.11 CTRL.ESSXSWI1 Grounding switch indication (1) – 29GS-1
Table 14: CTRL.ESSXSWI1 Grounding switch indication (1) – 29GS-1
BitA
RegA IEC 61850 name SA name Description Values
CTRL.ESSXSWI1 POSITION
2801 175.01 .Pos.stVal.Close - Close bit 1=Close
2802 175.02 .Pos.stVal.Open - Open bit 1=Open
2803 175.03 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
2.3.1.12 CTRL.ESSXSWI2 Grounding switch indication (2) – 29GS-2
Table 15: CTRL.ESSXSWI2 Grounding switch indication (2) – 29GS-2
BitA
RegA IEC 61850 name SA name Description Values
CTRL.ESSXSWI2 POSITION
2807 175.07 .Pos.stVal.Close - Close bit 1=Close
2808 175.08 .Pos.stVal.Open - Open bit 1=Open
2809 175.09 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
Section 2 1MAC252756-MB B
Modbus data mappings
24 REM615 ANSI
Point List Manual