2.3.1.13 CTRL.ESXSWI1 Grounding switch control (1) – 29GS-1
Table 16: CTRL.ESXSWI1 Grounding switch control (1) – 29GS-1
BitA
RegA IEC 61850 name SA name Description Values
CTRL.ESXSWI1 POSITION
3496 218.08 .Pos.stVal.Close - Close bit 1=Close
3497 218.09 .Pos.stVal.Open - Open bit 1=Open
3498 218.10 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
3499 218.11 .Pos.stSeld - Control selected 1=Selected
CTRL.ESCILO1
3500 218.12 .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
3501 218.13 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
CTRL.ESXSWI1
3502 218.14 .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
3503 218.15 .mcd
3504 219.00 .BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
3505 219.01 .mcd
CTRL.ESCILO1
3506 219.02 .ItlByps.stVal ITL_BYPASS Interlock bypass 1=Bypass
3507 219.03 .mcd
2.3.1.14 LD0.ARCSARC1 Arc protection (1) – AFD-1
Table 17: LD0.ARCSARC1 Arc protection (1) – AFD-1
BitA
RegA IEC 61850 name SA name Description Values
LD0.ARCSARC11
2978 186.02 .FADet.stVal ARC_FLT_DET Arc detected 1=Detected
2979 186.03 .mcd
LD0.ARCPTRC11
2982 186.06 .Op.general TRIP Stage trip 1=Trip
2983 186.07 .mcd
1MAC252756-MB B Section 2
Modbus data mappings
REM615 ANSI 25