2.3.1.15 LD0.ARCSARC2 Arc protection (2) – AFD-2
Table 18: LD0.ARCSARC2 Arc protection (2) – AFD-2
BitA
RegA IEC 61850 name SA name Description Values
LD0.ARCSARC21
2984 186.08 .FADet.stVal ARC_FLT_DET Arc detected 1=Detected
2985 186.09 .mcd
LD0.ARCPTRC21
2988 186.12 .Op.general TRIP Stage trip 1=Trip
2989 186.13 .mcd
2.3.1.16 LD0.ARCSARC3 Arc protection (3) – AFD-3
Table 19: LD0.ARCSARC3 Arc protection (3) – AFD-3
BitA RegA IEC 61850 name SA name Description Values
LD0.ARCSARC31
2990 186.14 .FADet.stVal ARC_FLT_DET Arc detected 1=Detected
2991 186.15 .mcd
LD0.ARCPTRC31
2994 187.02 .Op.general TRIP Stage trip 1=Trip
2995 187.03 .mcd
2.3.1.17 LD0.CCBRBRF1 Circuit breaker failure protection (1) – 50BF-1
Table 20: LD0.CCBRBRF1 Circuit breaker failure protection (1) – 50BF-1
BitA
RegA IEC 61850 name SA name Description Values
LD0.CCBRBRF1
2828 176.12 .Str.general CB_FAULT_AL Timer running 1=Running
2829 176.13 .mcd
2830 176.14 .OpEx.general TRBU Fail, external trip 1=Ext.trip
2831 176.15 .mcd
2832 177.00 .OpIn.general TRRET Internal re-trip 1=Re-trip
2833 177.01 .mcd