2.3.1.18 LD0.CCSPVC1 Current circuit supervision (1) – CCM-1
Table 21: LD0.CCSPVC1 Current circuit supervision (1) – CCM-1
BitA
RegA IEC 61850 name SA name Description Values
LD0.CCSPVC1
2936 183.08 .SigFailAlm.stVal ALARM Alarm 1=Alarm
2937 183.09 .mcd
2938 183.10 .FailACirc.general FAIL Failure trip 1=Trip
2939 183.11 .mcd
2.3.1.19 LD0.CMMXU1 Three-phase current measurement (1) – IA, IB, IC
Table 22: LD0.CMMXU1 Three-phase current measurement (1) – IA, IB, IC
BitA RegA IEC 61850 name SA name Description Values
LD0.CMMXU1
2752 172.00 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
2753 172.01 .mcd
2754 172.02 .HiWrn.stVal HIGH_WARN High warning 1=Warning
2755 172.03 .mcd
2756 172.04 .LoWrn.stVal LOW_WARN Low warning 1=Warning
2757 172.05 .mcd
2758 172.06 .LoAlm.stVal LOW_ALARM Low alarm 1=Alarm
2759 172.07 .mcd
2.3.1.20 LD0.DEFLPDEF1 Directional ground-fault protection, low stage (1) –
67/51N-1
Table 23: LD0.DEFLPDEF1 Directional ground-fault protection, low stage (1) – 67/51N-1
BitA
RegA IEC 61850 name SA name Description Values
LD0.DEFLPTOC1
2900 181.04 .Str.general PICKUP Stage pickup 1=Pickup
2901 181.05 .mcd
2902 181.06 .Op.general TRIP Stage trip 1=Trip
2903 181.07 .mcd
1MAC252756-MB B Section 2
Modbus data mappings
REM615 ANSI 27
Point List Manual