2.3.1.21 LD0.DOPPDPR1 Reverse power/directional overpower protection (1) –
32O-1
Table 24: LD0.DOPPDPR1 Reverse power/directional overpower protection (1) – 32O-1
BitA
RegA IEC 61850 name SA name Description Values
LD0.DOPPDPR1
4076 254.12 .Str.general PICKUP Stage pickup 1=Pickup
4077 254.13 .mcd
4078 254.14 .Op.general TRIP Stage trip 1=Trip
4079 254.15 .mcd
2.3.1.22 LD0.DOPPDPR2 Reverse power/directional overpower protection (2) –
32O-2
Table 25: LD0.DOPPDPR2 Reverse power/directional overpower protection (2) – 32O-2
BitA RegA IEC 61850 name SA name Description Values
LD0.DOPPDPR2
4080 255 .Str.general PICKUP Stage pickup 1=Pickup
4081 255.1 .mcd
4082 255.2 .Op.general TRIP Stage trip 1=Trip
4083 255.3 .mcd
2.3.1.23 LD0.DOPPDPR3 Reverse power/directional overpower protection (3)
Table 26: LD0.DOPPDPR3 Reverse power/directional overpower protection (3)
BitA
RegA IEC 61850 name SA name Description Values
LD0.DOPPDPR3
4084 255.4 .Str.general PICKUP Stage pickup 1=Pickup
4085 255.5 .mcd
4086 255.6 .Op.general TRIP Stage trip 1=Trip
4087 255.7 .mcd